What Is Cv Value? Valve Flow Coefficient
Cv (flow coefficient) is a dimensionless number that expresses a valve’s flow capacity. It is defined as the number of US gallons per minute of water at 60 degF that flows through a fully open valve with a pressure drop of 1 psi. A valve with Cv = 100 passes 100 US GPM of water at 1 psi differential pressure.
Cv is the single most important parameter for sizing control valves. It determines whether the valve is large enough to pass the required flow at the available pressure drop.
Cv Definition and Formula
| Parameter | Symbol | Unit |
|---|---|---|
| Flow coefficient | Cv | US GPM at 1 psi delta-P (water, 60 degF) |
| Flow rate | Q | US gallons per minute (GPM) |
| Pressure drop | delta-P | psi (P1 - P2) |
| Specific gravity | G | Relative to water (water = 1.0) |
Liquid flow formula:
Cv = Q x sqrt(G / delta-P)
Example: A valve must pass 200 GPM of water (G=1.0) with 4 psi pressure drop.
Cv = 200 x sqrt(1.0 / 4) = 200 x 0.5 = 100
A valve with rated Cv of 100 or higher is required.
Cv Values by Valve Type and Size
| Valve Type | 2” | 4” | 6” | 8” | 12” |
|---|---|---|---|---|---|
| Full bore ball valve | 135 | 640 | 1,470 | 2,640 | 5,400 |
| Reduced bore ball valve | 90 | 400 | 900 | 1,600 | 3,600 |
| Gate valve (full open) | 120 | 590 | 1,350 | 2,500 | 5,100 |
| Globe valve | 30 | 110 | 210 | 340 | 700 |
| Butterfly valve (90 deg open) | 80 | 480 | 1,200 | 2,200 | 4,800 |
Globe valves have the lowest Cv per size because of their tortuous S-shaped flow path. Full bore ball and gate valves have the highest Cv because of their unobstructed through-bore.
Cv and Valve Sizing
The ISA/IEC 60534 standard provides comprehensive sizing equations for control valves:
| Service | Sizing Considerations |
|---|---|
| Liquid (non-flashing) | Cv = Q x sqrt(G / delta-P) |
| Liquid (flashing/cavitating) | Correction for FL (pressure recovery factor) |
| Gas/vapor | Different formula using specific heat ratio, upstream pressure |
| Steam | Empirical formula using steam tables |
| Two-phase | Sum of liquid and gas Cv requirements |
Cv at Partial Opening (Flow Characteristic)
Control valves do not operate at full-open Cv. The relationship between valve opening and Cv depends on the flow characteristic:
| Characteristic | Behavior | Application |
|---|---|---|
| Linear | Cv proportional to % open (50% open = 50% Cv) | Liquid level control |
| Equal percentage | Small Cv change at low opening; large change at high opening | Most process control loops |
| Quick opening | Large Cv change at low opening; small change at high opening | On/off, relief bypass |
Cv vs Kv
| Parameter | Cv | Kv |
|---|---|---|
| Units | US gallons per minute | Cubic meters per hour |
| Test medium | Water at 60 degF (15.6 degC) | Water at 5-30 degC |
| Pressure drop | 1 psi | 1 bar |
| Primary usage | North America, oil and gas | Europe, international |
| Conversion | Cv = 1.156 x Kv | Kv = 0.865 x Cv |
Oversizing and Undersizing
| Problem | Cause | Consequence |
|---|---|---|
| Undersized | Cv too low for required flow | Valve fully open, no control range; cannot deliver design flow |
| Oversized | Cv much higher than required | Valve operates at very low opening; poor control, high wear, noise |
| Correct sizing | Cv provides 60-80% opening at normal flow | Full control range available; good rangeability |
Leave a Comment
Have a question or feedback? Send us a message.