A stroke test verifies that an actuated valve moves from its normal position to its fail-safe position and back within the required time. Stroke testing is required for emergency shutdown valves (ESDVs), blowdown valves, and control valves in safety instrumented systems (SIS).
Full Stroke Test Procedure
Step
Action
Details
1
Review valve data sheet
Confirm the valve tag, fail-safe action (fail-close or fail-open), required stroke time, and actuator type.
2
Notify operations
Coordinate with the control room. A full stroke test will interrupt the process flow or isolate equipment. Use a bypass if available.
3
Verify initial position
Confirm the valve is in its normal operating position. Record the position feedback (open/close limit switch status) on the DCS/SIS.
4
Initiate the stroke
Send the trip command from the SIS or use the solenoid valve manual override. For pneumatic actuators, vent the air supply to simulate a fail-safe trip.
5
Measure stroke time
Using a stopwatch or the SIS time-stamped diagnostics, measure the time from trip command to full travel (confirmed by the end-of-travel limit switch).
6
Verify end position
Confirm the valve reaches the full fail-safe position (fully closed or fully open). Check the position indicator and limit switches.
7
Return to normal
Reset the trip command and verify the valve returns to its normal operating position. Measure the return stroke time.
8
Record and evaluate
Document stroke times, limit switch operation, and any anomalies (hesitation, sticking, slow response). Compare against acceptance criteria.
Partial Stroke Test (PST)
A partial stroke test moves the valve 10-20% from its normal position without fully closing or opening, allowing proof testing without process interruption.
Parameter
Full Stroke Test (FST)
Partial Stroke Test (PST)
Valve travel
100% (full open to full close or vice versa)
10-20% of full travel
Process interruption
Yes (requires bypass or shutdown)
No (valve remains in service)
Detectable failures
All (stuck valve, slow response, broken spring, failed solenoid)
Most (stuck valve, slow initial response), but not end-of-travel issues
SIL credit
Full proof test coverage
Partial proof test coverage (typically 60-80% diagnostic coverage)
Frequency
Annually (or per SIL assessment)
Monthly to quarterly
Automation
Manual or automated
Typically automated via smart positioner or SIS
Acceptance Criteria
Parameter
Typical Requirement
Full stroke time (close)
Depends on valve size; typically 2-10 seconds for ESDVs (per API 6D and project spec)
Full stroke time (open)
Typically equal to or longer than close time
Stroke time tolerance
+/- 10% of the specified time (or per project specification)
Limit switch operation
Both open and close limit switches must activate within 2% of end position
Valve seat tightness
Class V or Class VI per API 598 / FCI 70-2 (for tight shutoff valves)
No sticking or hesitation
Valve must move smoothly without stops, jerks, or excessive delay
Key Points
Stroke testing of safety-critical valves is governed by IEC 61508/61511 for SIL-rated systems.
Leave a Comment
Have a question or feedback? Send us a message.