Skip to content

Pipe Schedule Wall Thickness

The pipe schedule number determines the wall thickness of a pipe for a given nominal pipe size (NPS). Higher schedule numbers indicate thicker walls and higher pressure ratings. The following chart shows wall thickness values in millimeters for standard pipe schedules from Sch 5S to XXS, per American Standard B36.10M and American Standard B36.19M.

Pipe Schedule Wall Thickness Chart (mm)

NPSOD (mm)Sch 5SSch 10SSch 10Sch 20Sch 30Sch 40/STDSch 60Sch 80/XSSch 100Sch 120Sch 140Sch 160XXS
1/2”21.31.652.11---2.77-3.73---4.787.47
3/4”26.71.652.11---2.87-3.91---5.567.82
1”33.41.652.77---3.38-4.55---6.359.09
1-1/4”42.21.652.77---3.56-4.85---6.359.70
1-1/2”48.31.652.77---3.68-5.08---7.1410.15
2”60.31.652.77---3.91-5.54---8.7411.07
2-1/2”73.02.113.05---5.16-7.01---9.5314.02
3”88.92.113.05---5.49-7.62---11.1315.24
3-1/2”101.62.113.05---5.74-8.08----16.15
4”114.32.113.05---6.02-8.56---13.4917.12
5”141.32.773.40---6.55-9.53---15.8819.05
6”168.32.773.40---7.11-10.97---18.2621.95
8”219.12.773.76-6.357.048.1810.3112.7015.0918.2620.6223.0122.23
10”273.13.404.19-6.357.809.2712.7012.7015.0921.4425.4028.5825.40
12”323.93.964.57-6.358.389.5314.2712.7017.4821.4425.4033.3225.40
14”355.63.964.78-7.929.539.5315.0912.7019.0523.8327.7935.71-
16”406.44.194.78-7.929.539.5316.6612.7021.4426.1930.9636.53-
18”457.24.194.78-7.9211.139.5317.4812.7023.8329.3634.9339.67-
20”508.04.785.54-9.5312.709.5320.6212.7026.1932.5438.1044.45-
24”609.65.546.35-9.5314.279.5324.6112.7030.9638.8946.0252.37-

Notes

  • Wall thickness values are given in millimeters (mm) and are based on American Standard B36.10M (carbon and alloy steel pipes) and American Standard B36.19M (stainless steel pipes).
  • The “S” suffix (Sch 5S, Sch 10S) designates stainless steel pipe schedules per American Standard B36.19M.
  • STD (Standard), XS (Extra Strong), and XXS (Double Extra Strong) are legacy designations. For NPS 1/2” to 10”, STD equals Sch 40 and XS equals Sch 80. For NPS 12” and above, STD and XS have fixed wall thicknesses (9.53 mm and 12.70 mm, respectively) that do not correspond to Sch 40 and Sch 80.
  • A dash (-) indicates that no standard wall thickness is defined for that combination of pipe size and schedule.
  • For sizes NPS 14” and above, XXS is generally not defined per American Standard B36.10M.
  • Actual wall thickness may vary within the manufacturing tolerance specified by the applicable product standard (e.g., ASTM A106, API 5L).